| Standert | IEC/EN 60898-1 | ||||
| Poalnûmer | 1P, 1P+N, 2P, 3P, 3P+N, 4P | ||||
| Nominale spanning | AC 230V/400V | ||||
| Rated Current (A) | 1A,2A,3A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A | ||||
| Trippingkromme | B, C, D | ||||
| Rated koartslutingskapasiteit (lcn) | 6000A | ||||
| Nominale frekwinsje | 50/60Hz | ||||
| Nominale ympulsbehâldspanning Uimp | 4kV | ||||
| Ferbiningsterminal | Pylderterminal mei klem | ||||
| Mechanysk libben | 20.000 syklusen | ||||
| Elektryske libbensduur | 4000 syklusen | ||||
| Beskermingsgraad | IP20 | ||||
| Ferbiningskapasiteit | Fleksibele geleider 35mm² | ||||
| Stive geleider 50mm² | |||||
| Ynstallaasje | Op symmetryske DIN-rail 35mm | ||||
| Paneelmontage |
| Toets | Trippingstype | Teststroom | Begjinnende steat | Útskeakeltiid of Net-útskeakeltiidfoarsjenner | |
| a | Tiidfertraging | 1.13 yn | Kâld | t≤1h(Yn≤63A) t≤2h(ln>63A) | Gjin útsteken |
| b | Tiidfertraging | 1.45 yn | Nei in test | t<1h(Yn≤63A) t<2o(Yn>63A) | Trippen |
| c | Tiidfertraging | 2.55 yn | Kâld | 1s 1s | Trippen |
| d | B-kromme | 3 yn | Kâld | t≤0.1s | Gjin útsteken |
| C-kromme | 5 yn | Kâld | t≤0.1s | Gjin útsteken | |
| D-kromme | 10 yn | Kâld | t≤0.1s | Gjin útsteken | |
| e | B-kromme | 5 yn | Kâld | t≤0.1s | Trippen |
| C-kromme | 10 yn | Kâld | t≤0.1s | Trippen | |
| D-kromme | 20 yn | Kâld | t≤0.1s | Trippen | |