CJ: Undernimmingskoade
M: Moulded case circuit breaker
1: Untwerp nr
□: Nominearre stroom fan frame
□: Breekkapasiteit karakteristike koade / S jout standert type oan (S kin wurde weilitten) H jout heger type oan
Opmerking: D'r binne fjouwer soarten neutrale peal (N-poal) foar produkt mei fjouwer fazen. De neutrale peal fan type A is net foarsjoen fan oerstreamende tripping-elemint, it is altyd ynskeakele, en it is net yn- of útskeakele tegearre mei oare trije peallen.
De neutrale peal fan type B is net foarsjoen fan oerstreamende tripping elemint, en it is yn- of útskeakele tegearre mei oare trije peallen (de neutrale peal wurdt ynskeakele foardat se útskeakele wurde) De neutrale peal fan type C is foarsjoen fan oer- aktueel útskeakele elemint, en it is yn- of útskeakele tegearre mei oare trije peallen (de neutrale peal wurdt ynskeakele foardat se útskeakele wurde) De neutrale peal fan type D is foarsjoen fan oerstreamende útskeakele elemint, it is altyd ynskeakele en is net skeakele op of út tegearre mei oare trije peallen.
Accessory namme | Elektroanyske release | Compound release | ||||||
Auxiliary kontakt, ûnder spanning release, alam kontakt | 287 | 378 | ||||||
Twa helpkontaktsets, alarmkontakt | 268 | 368 | ||||||
Shunt release, alarm kontakt, helptiidwurd kontakt | 238 | 348 | ||||||
Under spanning release, alarm kontakt | 248 | 338 | ||||||
Helpkontakt alarm kontakt | 228 | 328 | ||||||
Shunt release alarm kontakt | 218 | 318 | ||||||
Helpkontakt ûnder spanning frijlitting | 270 | 370 | ||||||
Twa helpkontaktsets | 260 | 360 | ||||||
Shunt release ûnder spanning release | 250 | 350 | ||||||
Shunt release helptiidwurd kontakt | 240 | 340 | ||||||
Under-voltage release | 230 | 330 | ||||||
Hulpkontakt | 220 | 320 | ||||||
Shunt release | 210 | 310 | ||||||
Alarm kontakt | 208 | 308 | ||||||
Gjin accessoire | 200 | 300 |
1 Rated wearde fan circuit breakers | ||||||||
Model | Imax (A) | Spesifikaasjes (A) | Nominearre wurkspanning (V) | Nominearre isolaasjespanning (V) | Icu (kA) | Ics (kA) | Oantal poalen (P) | Arcing ôfstân (mm) |
CJMM1-63S | 63 | 6,10,16,20 25,32,40, 50,63 | 400 | 500 | 10* | 5* | 3 | ≤50 |
CJMM1-63H | 63 | 400 | 500 | 15* | 10* | 3,4 | ||
CJMM1-100S | 100 | 16,20,25,32 40,50,63, 80.100 | 690 | 800 | 35/10 | 22/5 | 3 | ≤50 |
CJMM1-100H | 100 | 400 | 800 | 50 | 35 | 2,3,4 | ||
CJMM1-225S | 225 | 100.125, 160.180, 200.225 | 690 | 800 | 35/10 | 25/5 | 3 | ≤50 |
CJMM1-225H | 225 | 400 | 800 | 50 | 35 | 2,3,4 | ||
CJMM1-400S | 400 | 225.250, 315.350, 400 | 690 | 800 | 50/15 | 35/8 | 3,4 | ≤100 |
CJMM1-400H | 400 | 400 | 800 | 65 | 35 | 3 | ||
CJMM1-630S | 630 | 400.500, 630 | 690 | 800 | 50/15 | 35/8 | 3,4 | ≤100 |
CJMM1-630H | 630 | 400 | 800 | 65 | 45 | 3 | ||
Opmerking: As de testparameters foar de 400V, 6A sûnder ferwaarming frijlitte |
2 Omkearde tiidbrekkende operaasje karakteristyk as elke poal fan oerstreaming frijlitting foar machtferdieling tagelyk wurdt oandreaun | ||||||||
Item fan test Aktueel (I/In) | Test tiid gebiet | Inisjele steat | ||||||
Non-tripping hjoeddeistige 1.05In | 2h(n>63A), 1h(n<63A) | Kâlde steat | ||||||
Tripping current 1.3In | 2h(n>63A), 1h(n<63A) | Gean fuort fuort neidat No.1 test |
3 Inverse tiidbrekkende operaasje karakteristyk as elke poal fan oer- hjoeddeistige release foar motor beskerming wurdt oandreaun tagelyk. | ||||||||
Setting Aktuele Konvinsjonele tiid Initial State | Noat | |||||||
1.0 yn | >2h | Kâlde steat | ||||||
1.2 yn | ≤2h | Fuort fuort nei de No.1 test | ||||||
1.5 yn | ≤4 min | Kâlde steat | 10≤In≤225 | |||||
≤8 min | Kâlde steat | 225≤In≤630 | ||||||
7.2 yn | 4s≤T≤10s | Kâlde steat | 10≤In≤225 | |||||
6s≤T≤20s | Kâlde steat | 225≤In≤630 |
4 It karakteristyk fan 'e instantane operaasje fan circuit breaker foar macht distribúsje sil wurde ynsteld as 10in + 20%, en de ien fan circuit breaker foar motor beskerming sil wurde ynsteld as 12ln ± 20% |
CJMM1-63, 100, 225, Outline en ynstallaasje grutte (Front board ferbining)
Grutte (mm) | Model Code | |||||||
CJMM1-63S | CJMM1-63H | CJMM1-63S | CJMM1-100S | CJMM1-100H | CJMM1-225S | CJMM1-225 | ||
Outline maten | C | 85,0 | 85,0 | 88,0 | 88,0 | 102.0 | 102.0 | |
E | 50,0 | 50,0 | 51.0 | 51.0 | 60,0 | 52.0 | ||
F | 23.0 | 23.0 | 23.0 | 22.5 | 25.0 | 23.5 | ||
G | 14.0 | 14.0 | 17.5 | 17.5 | 17.0 | 17.0 | ||
G1 | 6.5 | 6.5 | 6.5 | 6.5 | 11.5 | 11.5 | ||
H | 73,0 | 81,0 | 68,0 | 86,0 | 88,0 | 103.0 | ||
H1 | 90,0 | 98,5 | 86,0 | 104.0 | 110,0 | 127,0 | ||
H2 | 18.5 | 27.0 | 24.0 | 24.0 | 24.0 | 24.0 | ||
H3 | 4.0 | 4.5 | 4.0 | 4.0 | 4.0 | 4.0 | ||
H4 | 7.0 | 7.0 | 7.0 | 7.0 | 5.0 | 5.0 | ||
L | 135,0 | 135,0 | 150,0 | 150,0 | 165,0 | 165,0 | ||
L1 | 170,0 | 173,0 | 225,0 | 225,0 | 360,0 | 360,0 | ||
L2 | 117,0 | 117,0 | 136,0 | 136,0 | 144,0 | 144,0 | ||
W | 78,0 | 78,0 | 91.0 | 91.0 | 106,0 | 106,0 | ||
W1 | 25.0 | 25.0 | 30.0 | 30.0 | 35,0 | 35,0 | ||
W2 | - | 100,0 | - | 120,0 | - | 142,0 | ||
W3 | - | - | 65,0 | 65,0 | 75,0 | 75,0 | ||
Ynstallearje Maten | A | 25.0 | 25.0 | 30.0 | 30.0 | 35,0 | 35,0 | |
B | 117,0 | 117,0 | 128,0 | 128,0 | 125,0 | 125,0 | ||
od | 3.5 | 3.5 | 4.5 | 4.5 | 5.5 | 5.5 |
CJMM1-400,630,800, Outline en ynstallaasjegrutte (ferbining oan 'e foarkant)
Grutte (mm) | Model Code | |||||||
CJMM1-400S | CJMM1-630S | |||||||
Outline maten | C | 127 | 134 | |||||
C1 | 173 | 184 | ||||||
E | 89 | 89 | ||||||
F | 65 | 65 | ||||||
G | 26 | 29 | ||||||
G1 | 13.5 | 14 | ||||||
H | 107 | 111 | ||||||
H1 | 150 | 162 | ||||||
H2 | 39 | 44 | ||||||
H3 | 6 | 6.5 | ||||||
H4 | 5 | 7.5 | ||||||
H5 | 4.5 | 4.5 | ||||||
L | 257 | 271 | ||||||
L1 | 465 | 475 | ||||||
L2 | 225 | 234 | ||||||
W | 150 | 183 | ||||||
W1 | 48 | 58 | ||||||
W2 | 198 | 240 | ||||||
A | 44 | 58 | ||||||
Ynstallearje Maten | A1 | 48 | 58 | |||||
B | 194 | 200 | ||||||
Od | 8 | 7 |
Back Board Connection Cut-out Diagram Plug In
Grutte (mm) | Model Code | ||||||
CJMM1-63S CJMM1-63H | CJMM1-100S CJMM1-100H | CJMM1-225S CJMM1-225H | CJMM1-400S | CJMM1-400H | CJMM1-630S CJMM1-630H | ||
Maten fan Back Board Connection Plug yn Type | A | 25 | 30 | 35 | 44 | 44 | 58 |
od | 3.5 | 4,5*6 djip gat | 3.3 | 7 | 7 | 7 | |
od1 | - | - | - | 12.5 | 12.5 | 16.5 | |
od2 | 6 | 8 | 8 | 8.5 | 9 | 8.5 | |
oD | 8 | 24 | 26 | 31 | 33 | 37 | |
oD1 | 8 | 16 | 20 | 33 | 37 | 37 | |
H6 | 44 | 68 | 66 | 60 | 65 | 65 | |
H7 | 66 | 108 | 110 | 120 | 120 | 125 | |
H8 | 28 | 51 | 51 | 61 | 60 | 60 | |
H9 | 38 | 65,5 | 72 | - | 83,5 | 93 | |
H10 | 44 | 78 | 91 | 99 | 106,5 | 112 | |
H11 | 8.5 | 17.5 | 17.5 | 22 | 21 | 21 | |
L2 | 117 | 136 | 144 | 225 | 225 | 234 | |
L3 | 117 | 108 | 124 | 194 | 194 | 200 | |
L4 | 97 | 95 | 9 | 165 | 163 | 165 | |
L5 | 138 | 180 | 190 | 285 | 285 | 302 | |
L6 | 80 | 95 | 110 | 145 | 155 | 185 | |
M | M6 | M8 | M10 | - | - | - | |
K | 50.2 | 60 | 70 | 60 | 60 | 100 | |
J | 60,7 | 62 | 54 | 129 | 129 | 123 | |
M1 | M5 | M8 | M8 | M10 | M10 | M12 | |
W1 | 25 | 35 | 35 | 44 | 44 | 58 |
Yn MCCB ferwiist rated koartsluting brekking kapasiteit nei de brekking kapasiteit ûnder spesifisearre betingsten.Nei de oantsjutte testproseduere is it nedich om te beskôgje dat de circuit breaker syn nominearre stroom bliuwt.Om te foldwaan oan 'e behoeften fan ferskate brûkers, ferdiele in protte circuit breaker-fabrikanten no de koartsluting-breaking-kapasiteit fan deselde shell-beoardielingsstroom yn ferskate nivo's, en brûkers kinne de passende circuit breaker kieze neffens har behoeften fan it minimum oant it maksimum hjoeddeistige circuit breakers.Se binne sa gewoan en fûn yn hast elk gebou of struktuer dat se faaks as fanselssprekkend wurde nommen.Dochs spylje se in essensjele rol yn ús elektrysk netsysteem en moatte wurde ûnderhâlden om by te hâlden mei de lêste feiligensnoarmen.
MCCB's jouwe in daliks antwurd op in koartslutingsfoutstream, basearre op it prinsipe fan elektromagnetisme.De MCCB befettet in solenoïde-spoel dy't in lyts elektromagnetysk fjild genereart as de stroom troch de MCCB giet.De MCCB brûkt in temperatuergefoelige apparaat (it termyske elemint) mei in aktueel gefoelich elektromagnetysk apparaat (it magnetysk elemint) om it reismeganisme (thermysk magnetysk) te leverjen foar termyske beskerming en isolaasjedoelen.Tidens normale operaasje of normale omstannichheden is it elektromagnetyske fjild dat wurdt generearre troch de solenoïde-spul ferwaarlooslik.As der lykwols in koartslutingsfout optreedt yn 'e sirkwy, begjint in grutte stroom troch de solenoïde te rinnen en as gefolch wurdt in sterk elektromagnetysk fjild oprjochte dat de reisbalke oanlûkt en de kontakten iepenet.