IEC Electrical | 150 | 275 | 320 | 385 | 440 | ||
Nominale AC spanning (50/60Hz) | 120V | 230V | 230V | 230V | 400V | ||
Maksimum trochgeande wurkspanning (AC) | (LN) | Uc | 150V | 275V | 320V | 385V | 440V |
(N-PE) | Uc | 255V | |||||
Nominale ûntlaadstroom (8/20μs) | (LN)/(N-PE) | In | 20kV/20kA | ||||
Maksimum ûntlaadstroom (8/20μs) | (LN)/(N-PE) | Imax | 40kA/40kA | ||||
Voltage Protection Level | (LN)/(N-PE) | Up | 1.0kV/1.5kV | 1.5kV/1.5kV | 1.6kV/1.5kV | 1.8kV/1.5kV | 2.0kV/1.5kV |
Folgje aktuele ûnderbrekkingswurdearring | (N-PE) | Ifi | 100 ARMS | ||||
Reaksjetiid | (LN)/(N-PE) | tA | <25ns/<100ns | ||||
Back-up fuse (max) | 125A gL/gG | ||||||
Koartesluting hjoeddeistige beoardieling (AC) | (LN) | ISCCR | 20 kA / 50 kA | ||||
TOV Standert 5s | (LN) | UT | 180V | 335V | 335V | 335V | 580V |
TOV 120 min | (LN) | UT | 230V | 440V | 440V | 440V | 765V |
wize | Wjerstean | Safe Fail | Safe Fail | Safe Fail | Safe Fail | ||
TOV Standert 200ms | (N-PE) | UT | 1200V | ||||
Operating Temperatur Range | -40ºF oant +158ºF[-40ºC oant +70ºC] | ||||||
Talitten Operating Feuchte | Ta | 5%…95% | |||||
Atmosfearyske druk en hichte | RH | 80k Pa..106k Pa/-500m..2000m | |||||
Terminal Screw Torque | Mmax | 39.9 lbf-in[4.5 Nm] | |||||
Dirigint Dwarssneed (max) | 2 AWG (Solid, Stranded) / 4 AWG (Fleksibel) | ||||||
35 mm2 (Solid, Strând) / 25 mm2 (Fleksibel) | |||||||
Montage | 35 mm DIN-rail, EN 60715 | ||||||
Beskermingsgraad | IP 20 (ynboud) | ||||||
Húsfesting Materiaal | Thermoplastic: Extinguishing Degree UL 94 V-0 | ||||||
Termyske beskerming | Ja | ||||||
Operating State / Fault Yndikaasje | Grien ok / Reade defekt | ||||||
Kontakten op ôfstân (RC) / RC Switching Kapasiteit | Fakultatyf | ||||||
RC Conductor Dwarsseksje (max) | AC: 250V/0.5A;DC:250V/0.1A;125V/0.2A;75V/0.5A | ||||||
16 AWG (solid) / 1,5 mm2 (solid) |